文档介绍:本设计是根据原始资料对矿35kV变电所的一次系统及部分二次系统的初步设计。
利用需用系数法算出了不同电压等级下的计算负荷,选择了低压变压器并且选择了主变压器;并对供电一次、二次系统并做了短路计算,为系统的安全运行选择可靠的继电保护;以及主控室控制屏的选择,保护接地系统和防过电压方案的确定,还对变电所室内外的布置作出合理的设计。通过本设计为矿山供电及安全生产保驾护航。
关键词:变电所设计需用系数短路整定继电保护过电压
Abstract
The design is according to the preliminary design of the original data on the 35kV substation mine a system and some secondary system.
Required coefficient method to calculate putational load under different voltage levels, choose a low-voltage transformer and select the main transformer; and supply primary and secondary systems and short-circuit calculations, and for the safe operation of the system to select a reliable relay protection; as well as the choice of the main control room screen to protect the grounding system and anti-voltage program, and also make the rational design of substation indoor and outdoor layout. Through the design for the production of mine supply and safety escort.
Keywords: substation design required coefficient of short circuit tuning relay over voltage
目录
1 概述 1
2 负荷计算与变压器选择 2
负荷分组与计算 2
各个设备的负荷计算 2
低压变压器的选择与损耗计算 5
cosΦ补偿与电容器柜选择 7
6kV母线上补偿前的总负荷 7
cosΦ补偿 7
电容器柜的选择 8
补偿后6kV侧的计算负荷与功率因数 8
主变压器的选择 9
选择主变压器 9
cosφ35及全矿电耗、吨煤电耗的计算 9
补偿后主变压器损耗计算 9
补偿后35kV侧全矿总负荷与cosφ35 10
全矿电耗与吨煤电耗 10
计算选择结果汇总 10
3 供电系统拟定与短路计算 11
供电系统的拟定 11
确定35kV进线回数 11
确定35kV、6kV主结线 11
负荷分配 11
下井电缆回数确定 11
供电系统简图 12
系统短路计算 12
选取基准量 13
计算各元件电抗标幺值 13
各短路点的短路计算 14
限流电抗器的选择 18
井下负荷计算 18
选择限流电抗器 18
选用电抗器的校验 18
短路参数表(含加电抗器后的修正) 20
4 变电所电气设备选择 21
35kV电气设备的选择 21
35kV断路器的选择 21
35kV隔离开关的选择 22
35kV电压互感器的选择 22
35kV避雷器的选择 22
6kV电气设备的选择 22
高压开关柜的选择 22
零序电流互感器的选择 23
电压互感器、避雷器及熔断器的选择 24
电抗器出线隔离开关的选择 24
35kV输电线及母线的选择 25
35kV母线的选择 25
35kV输电线的选择 25
6kV母线、电缆及架空线的选择 26
6kV母线的选择 26
母线瓷