文档介绍:某厂房柱纠偏加固技术
张永青吴坚强
( 江苏沙钢集团有限公司张家港 215625) ( 江苏省建友工程项目管理咨询有限公司淮安 223800)
李今保赵启明
( 江苏东南特种技术工程有限公司南京 210008)
摘要: 对某厂房在设备基坑开挖过程中, 由于开挖不当, 造成基础桩、承台和柱发生偏移的问题, 分析
了事故原因, 着重对该工程混凝土柱纠偏加固技术进行了论述。
关键词: 纠偏外包钢加固平移监测
DEVIATION-RECTIFYING AND STRENGTHENING OF COLUMNS FOR A MILL BULLDING
Zhang Yongqing Wu Jianqiang
( Jiangsu Shagang Group Co. , Ltd Zhangjiagang 215625) ( Jiangsu Jianyou Project Management and Consultation Co. , Ltd Huaian 223800)
Li Jinbao Zhao Qiming
( Jiangsu Southeast Special Engineering Co. , Ltd Nanjing 210008)
Abstract : The sways of foundation piles, cushion caps and columns occurred due to unsuitable excavation of equipment
foundations for a mill builging. The causes were analyzed. It was described emphatically the deviation-rectifying and
strengthening technologies of the concrete columns for the mill building.
Keywords : deviation- rectifying steel plate encasement translation monitoring
云母, 具层理, 底部为泥炭质土, 层厚 010~ 11 80m。
1 工程概况» 淤泥质粉质黏土: 灰色, 流塑; 摇振反应中等, 切面欠
该厂房为一层轻钢结构厂房, 建于 2007 年 2 月, 长光滑~ 无光泽, 韧性及干强度低, 含少量有机质及腐植质, 夹
180m, 宽 54m, 高 151 0m, 建筑面积约15 309100m2 , 该结构基础粉土层, 层厚 5170~ 191 70m。
采用直径 400mm 的混凝土管桩基础, 桩长约 21m, 设计承载¼- 1 粉质黏土: 青灰色, 可塑, 含少量有机质及云母片,
力特征值 490kN, 柱、承台为钢筋混凝土结构, 屋面为轻钢结具层理, 无摇振反应, 稍光滑, 韧性及干强度中等, 层厚 0100
构, 跨度 27m。~ 1190m。
¼- 2 粉质黏土: 灰黄色, 可塑状态, 无摇振反应, 稍光滑,
2 问题的提出韧性及干强度中等, 局部粉粒含量高, 层厚 0100~ 7110m。
该厂房主体结构施