文档介绍:课程设计题目: 某冶金机械修造厂总降压变电所一次系统设计
目录
一基础资料..............................................................1
....................................................1
..............................................1
........................................................2
........................................................3
.................................................4
...............................................4
.........................................................6
:......................................................7
..........................................................8
............................................8
..................................................8
..............................................10
..........................................................12
..........................................................14
..................................................15
三、小结...................................................................16
四、参考文献...............................................................17
某冶金机械修造厂总降压变电所一次系统设计
一基础资料
生产任务及车间组成
本厂主要承担冶金系统的配件生产,生产规模为:铸钢件1万吨,铸铁件3千吨,锻件1千吨,铆焊件2千吨。
本厂车间组成如表1所示。
设计总平面布置图
全
2)全厂各车间负荷如表2所示,各车间均为380V的负荷,但有一部分为高压设备为6kV的负荷。
3)供用电协议
工厂与供电部门所签定的供用电协议主要内容如下
(1)工厂从供电部门用35千伏双回架空线引入本厂,其中一个作为工作电源,一个作为备用电源,两个电源不并列运行。(即不同时工作),供电部门短路容量为200MVA,该变电所距厂东侧8公里。
(2)在本厂的总降压变电所35千伏侧进行计算,。
本厂为三班工作制,最大有功负荷年利用小时数为6000小时,属于二级负荷。
:
根据基本资料,选择本厂最优供电电压等级。选择10kV。
电力变压器是变电所中最关键的一次设备,其主要功能是将电力系统的电能电压升高或降低,以利于电能的合理输送、分配和使用。在该厂采用两台变压器非并列运行,一台变压器工作,另一台变压器停止运行作为备用,当两台变压器并列运行时,其中每台变压器容量的选择应满足以下两个条件: =(~) 和≥,这里不涉及该种情况。
主接线方案:
确定车间的计算负荷,一般用需要系数法,车间设备的利用系数乘上设备容量即为车间低压用电设备的总设备容量,即车间低压侧的计算负荷(有功功率)。并可求出相应的计算负荷(无功功率及视在功率)。计算后填入表1.(确定相应的变压器容量)