文档介绍:中性点不接地系统中的铁磁谐振过电压探讨
刘丽萍
(包头供电局,内蒙古包头014030)
 【摘要】:铁磁谐振过电压是一种常见的内部过电压,多发生在中性点不直接接地的配电网中,但在中性点直接接地的高压电网中,这种事故也常有发生。本文列举几个典型事例从理论上阐述系统产生铁磁谐振的原理,并提出抑制谐振的方法,供广大电气运行人员参考。
【关键词】:中性点不接地系统、铁磁谐振、过电压、消谐措施
Treating of ferro-resonance of
isolated neutral system’s overvoltage
LIU Li-ping
Baotou Power supply , Baotou Inner Mongolia 14030
Abstract:Ferroresonance is an internal overvoltage,which always occurs in neutral isolated work, and sometimes also occurs in high work. The research developments on ferroresonance are analyzed,
including their fundamental principles, characteristics and some typical examples. It also introduces several treatments of ferroresonance eliminating and its principle. Finally the further research trends are proposed.
Key words:power system; ferroresonance; overvoltage; treatment of resonance eliminating
一、概述
我局仅农电系统直属的变电站有62座,供电母线200余条,这些变电站中压母线35kV系统和10kV系统均采用中性点不接地方式运行。随着高压用户的增加,用户进线高压计量柜不断增加,系统内电磁式电压互感器也相应增加,由于系统运行参数发生变化引发的铁磁谐振过电压故障给供电质量带来了一定危害。铁磁谐振过电压故障表现形式不同,损坏程度不一,因此,运行人员不好判断
故障原因。一但系统发生铁磁谐振现象,轻则使熔断器熔断、互感器线圈烧毁,重则使变压器和断路器套管发生过电压闪络或崩裂造成严重后果。系统在正常的稳定状态下运行时不会发生振荡,当系统某处发生故障或某种操作过程中使电网参数变化就可能激发铁磁谐振。
例如:
1、99年3月21日,6月17日轻质变先后两次B相接地,,,,引发母线工频谐振,烧坏母线电压互感器,两次的表象基本一致,
2、09年9月张家营变电站110kV系统用母联开关由Ⅰ母向Ⅱ母出线充电时,Ⅱ母电压互感器的电感和母线开关均压电容及母线对地电容形成谐振,造成A、B两相电压互感器烧坏喷油。与此同时,10kV系统也产生谐振,导致10kV电压互感器一次保险熔断,电压互感器一次绕组烧坏。
二、铁磁谐振产生的现象和机理
笔者根据多年工作