文档介绍:UPS系统配置方式及采用双母线供电方案建议
吴阿明
(浙江邮电职业技术学院浙江绍兴 312000)
摘要:从IDC和MDC对UPS供电要求出发,介绍了目前UPS冗余配置方式,分析“1+1”并联冗余供电方式的缺陷及风险,提出在不增加UPS系统设备的前提下,采用双母线供电的方案建议。
关键词:UPS 冗余配置供电方式单点瓶颈双母线
Mode of Configuration of the UPS System and the Proposal of Adopting the Electricity-supply Scheme Through Double Bus
Wu Aming
(Zhejiang Vocational & Technical College of Post and munications, Shaoxing, 312000, China)
Abstract: Based on the electricity supply required by IDC and MDC, the paper firstly presents the present-day redundant mode of configuration of the UPS, and then it analyzes the drawbacks and risks caused by the redundant, parallel-circuited, electricity-supply mode. The paper es up with the proposal of adopting the electricity-supply scheme through double bus on the premise of the absence of additional facilities of the UPS system.
Key words: UPS; redundancy; configuration; electricity-supply mode; “bottleneck”; double bus
通信用UPS系统是以冗余备份方式工作的。现在大型UPS电源MTBF可达20万小时以上,但并不能确保故障率为零,在UPS系统中可采用具有容错功能的冗余配置方案来解决这个问题。因此如何解决好多台UPS电源以同频、同相、同幅运行是实现多台UPS冗余供电的关键。从冗余式配置方案来看,有以下几种方式:
主机—从机型“热备份”UPS供电方式;
直接并机冗余UPS供电方式;
双总线冗余供电方式;
一、主机—从机型“热备份”UPS供电方式
这是缘于UPS电源的锁相同步控制技术还未完善到足以保证多台UPS的逆变器电源总是处于同相、同频的跟踪技术下常采用的方案。热备份冗余系统工作方式为两套UPS串联切换。正常运行时,只有主UPS给关键负载供电,而另一台一直处于空载状态。如果主UPS有故障不能运行,它就切换到旁路,而备用UPS在过了大约2~8ms后自动接替工作。这种结构价格比较经济。但是,这种结构有许多单点故障。如果主UPS出了故障,那么另一台必须接替全部负载。这也就意味着在约8ms内,另一台必须把供电从0增加到100%,此方式的缺陷在于备