文档介绍:35KV电网继电保护设计
【摘要】
本次继电保护设计是35KV电网继电保护设计(多电源环网,单侧电源线路保护整定)。
本次设计中采用WXB—11C型微机保护对电网进行保护,首先介绍了电力系统继电保护的基础知识,然后根据给定35KV电网的接线图及参数,进行短路电流计算,制定出反应其输电线路上相间短路、接地短路故障的继电保护配置方案。通过对所配置的继电保护进行整定计算和校验,论证继电保护配置的正确性。并加装自动重合闸装置,提高供电可靠性。
关键词: 短路电流计算;电网继电保护;输电线路继电保护;重合闸
Abstract
This design is 35KV electric grid protection design (multi-power sources loop, single side power source line protection setting).
In this design using WXB-11C puter protection protects the work. First the electrical power system protection elementary knowledge is according to the wiring diagram and the parameter of the 35KV work, the short-circuit current is calculated. Protection equipment plan reflecting phase fault and earth fault on the transmission line are determined. Through setting calculation and verification of protection equipped, accuracy of protection equipment is proved. In order to improve power supply reliability, reclosing is equipped. The basis of the setting values worked out, the definite value lists of puter protection pleted.
Key words: protection; short-circuit current calculation; reclosing
目录
1 概述 1
1
1
1
1
1
2
35kV线路保护配置原则 2
35kV母线保护配置原则 2
35kV断路器保护配置原则 2
2 系统中各元件的主要参数计算 3
标幺制及标幺值计算方法 3
标幺制的概念 3
. 3
、双绕组变压器的参数计算 3
4
电阻参数计算 4
4
2. 4 输电线路参数的计算 4
3 中性点接地的选择 4
35KV中性点直接接地电网中线路的保护 5
5
、高频信号注意事项 5
5
距离保护各段的整定计算 6
4 短路电流的计算 8
8
9
5继电保护整定(以下电流值的单位为:KA;电压值的单位为:KV。) 10
11
保护5的Ⅰ段 11
保护5的Ⅱ段 11
保护5的Ⅲ段 12
12
保护3的Ⅰ段 12
保护3的Ⅱ段 12
保护3的Ⅲ段 13
13
保护1的Ⅰ段 13
保护1的Ⅱ段 13
保护1的Ⅲ段 13
14
保护2的Ⅰ段 14
保护2的Ⅱ段 15
保护2的Ⅲ段 15
、对保护4进行整定计算 15
保护4的Ⅰ段 15
保护4的Ⅱ段 16
保护4的Ⅲ