文档介绍:华为 TD 防雷接地方案说明文档密级
华为TD 防雷接地方案说明
1 直击雷防护..................................................................................................................................2
2 室外覆盖站点防雷接地方案.......................................................................................................2
方案1 (BBP530 室内,RRU 室外,-48V 供电)..................................................................2
方案2 (BBP530 室外,RRU 室外,220V 供电) .................................................................2
3 室内覆盖站点防雷接地方案.......................................................................................................3
方案1 (BBP530 室内,RRU 室内,-48V 供电)..................................................................3
方案2 (BBP530 室内,RRU 室内,220V 供电) .................................................................4
4 GPS 防雷接地方案........................................................................................................................5
室外部分GPS 馈线....................................................................................................................5
室内部分GPS 馈线....................................................................................................................6
5 部分设备防雷接地具体说明:::...................................................................................................8
直流屏蔽电源线的接地............................................................................................................8
天馈线的接地..........................................................................................................................10
2010-7-1 华为秘密,未经许可不得扩散第 1 页, 共 11 页
华为 TD 防雷接地方案说明文档密级
1 直击雷防护
天线、GPS 天线和和支架、馈线、GPS 馈线、RRU 、机房内各种设备(包括BBU 、DCDU 、
DDF 等)应在避雷针45 度角的保护范围之内。
2 室外覆盖站点防雷接地方案
方案1 (BBP530 室内,RRU 室外,-48V 供电)
接地对象接地要求接地线径
BBU530 通过挂耳与机柜搭接
DCDU-03B 通过接地线接到机柜接地点上 6 mm 2
机柜/机框/机架通过接地线接到机房保护地,不超过30 米 25 mm 2
E1/FE 线室内无需额外接地
RRU 电源线 1 电源线R