文档介绍:华中科技大学文华学院毕业设计(论文) 1 摘要本设计是武汉市某体育馆的舒适性中央空调的设计,建筑共分三层,此建筑用途有主会场、办公室、会议室、训练馆等。大会场及训练馆采用集中式的送风方式,对于周边的的办公室, 会议室等小房间则采用风机盘管加独立新风的送风方式, 对于三楼的几个小房间则采用家用空调分体机。空调冷源由两台螺杆式冷水机组提供,热源由锅炉经过板换后提供。冷冻水系统采用闭式水平同程式,垂直异程式。关键词: 集中式,风机盘管加独立新风,分体机。华中科技大学文华学院毕业设计(论文) 2 Abstract The design isa Stadium in Wuhan City, fort of central air-conditioning design, the building is divided into three layers, the building uses the main venue, offices, conference rooms, training hall. Field of the General Assembly and training center with centralized air around the office, conference room and small room fan coil independent fresh air supply air , home air conditioners for the third floor ofa small room body aircraft. Air conditioning cooling source is two screw chillers, heat from the boiler after the change of the board. The chilled water system using the closed level of the same program, the vertical different programs. Keywords: centralized, fan coil units, plus independent fresh air, split type. 华中科技大学文华学院毕业设计(论文) 3 第一章工程概况 工程概况: 本设计对象为武汉市某体育馆,场馆主要有: 办公室,会议室,训练馆,播音、积分、声控、以及主厅等。场馆主要分为三层,其中只有训练馆有地下层。工程位于武汉市,东经 114?13?,北纬 31?。总空调面积为 m 2。本工程空调设计的任务包括本场馆的中央空调系统的设计及通风设计。本中央空调系统设计要求能够实现夏季供冷, 并能满足人体的舒适性要求。 武汉市室外空调设计参数: 台站位置:北纬 31?,东经 114 ?13?。气象参数为: 夏季: 大气压: kpa 室外日平均温度: ℃室外相对湿度:79 % 室外干球温度: 35. 2 ℃室外湿球温度: ℃室外平均风速: 冬季: 大气压: kpa 采暖计算温度: -2 ℃空调计算温度: -5 ℃相对湿度: 76% 室外平均风速: m/s 室内空调主要设计参数表 室内设计参数房间名称温度℃(波动范围±2℃) 相对湿度% (波动范围± 10% ) 新风量 m 3 /(h ·人) 夏季冬季夏季冬季小办公室 26 18 60 40 30 值班室 26 18 60 40 30 大办公室 26 18 60 40 30 大训练用房 26 18 60 40 50 小训练用房 26 18 60 40 50 外管理室 26 18 60 40 25 控制室 26 18 60 40 25 华中科技大学文华学院毕业设计(论文) 4 电视转播室 26 18 60 40 30 会议室 26 18 60 40 40 售票室 26 18 60 40 25 内管理室 26 18 60 40 25 贵宾室 26 18 60 40 50 接待室 26 18 60 40 50 运动员休息 26 18 60 40 30 更衣室 26 18 60 40 20 医务室 26 18 60 40 50 裁判用房 26 18 60 40 30 新闻发布 26 18 60 40 30 尿检室 26 18 60 40 50 记者用房 26 18 60 40 25 冷饮吧台 26 18 60 40 20 播音室 26 18 60 40 30 灯控、声控室 26 18 60 40 30 计时、计分室 26 18 60 40 30 体育馆主厅 2