文档介绍:第六章 建筑电气工程
目 录
1. 配电箱(盘)安装 ··························································································· 1
电线、电缆导管和线槽敷设 ················································································ 9
.电线、电缆导管和线槽敷线· ············································································· 14
普通灯具安装 ······························································································· 19
插座、开关、风扇安装 ···················································································· 22
建筑照明通电运行 ························································································· 25
接地装置安装 ······························································································25
避雷引下线和变配电室接地下线敷设· ·································································31
建筑等电位连接 ···························································································· 33
北京惟明力通工程监理有限责任公司 建筑电气部分
配电箱(盘)安装
施工前期准备
序
控制项目
控
制
要
点
备 注
检查方式
号
安装配电箱(盘)孔洞预留尺寸是否合适、位臵是否符合图纸要求;
检查施工 2) 检查接地引线是否到位;
1 巡视
现场条件 3) 检查土建粉刷是否完毕,具备安装条件;
4)检查施工人员、工机具是否到位;
5)检查辅材是否合格
1)
再次核查箱(盘)防止二次搬运造成损坏;
检查箱
检查箱(盘)内元器件是否完好,有无锈蚀;
2
见证
2)
(盘)到
检查专用工具和易损件备品、门柜钥匙是否齐全,并妥
3)
场情况
善保管;
1)
检查有、无技术交底;
3
见证
检查技术
检查施工人员上岗资格证书;
2)
准备条件
检查施工单位质量保证体系能否正常开展工作;
3)
- 1 -
北京惟明力通工程监理有限责任公司 建筑电气部分
配电箱(盘)安装质量控制
序
控制项目
控
制
要
点
备 注
检查方式
号
见证
基础型钢安装的不直度小于 5mm/全长、水平度 5mm/全长、
基础型钢位臵误差及不平行度 5mm/全长;
安装 2) 基础型钢按装后, 其顶部宜高出抹平地面 10mm,并有明显可靠接地;
1)
箱(盘)安装在震动场所,应按设计要求采取防震措施;
2)
箱(盘)及内部设备与各构件间连接应牢固:
箱(盘) 3)
箱(盘)不宜与基础型钢焊死;
2见证
箱(盘)应安装牢固,其垂直偏差不应大于
3mm;
稳固4)
5)
箱(盘)暗装时,箱(盘)四周应无空隙,器面板四周边缘
应进贴墙面,箱体与建筑物、构筑物接触部分应涂防腐漆;
- 2 -
北