文档介绍:电力工程施工
安全操作规程
天津市新津建设有限公司
9月1日
1
目 录
1、停电作业········································1
2、带电作业········································2
3、暂时用电········································2
4、伐树、涉水、履冰··································3
5、装卸、运送······································6
6、挖沟、挖坑·······································9
7、拉线安装······································10
8、落地式变压器···································10
9、杆上设备······································13
10、现场灌注混凝土································13
11、组立杆塔······································13
12、放线、紧线·····································14
13、高空作业·····································16
14、箱式变电所安装································17
15、电缆敷设······································18
电力工程施工安全操作规程
1 停电作业
在带电杆塔上或带电设备附近作业时,作业人员活动范畴及 其所携带工具、材料等与带电体距离不大于表 规定期应停电 作业。
在带电线路杆塔上或带电设备附近作业安全距离
电压级别(kV)
安全距离(m)
电压级别(w)
安全距离(m)
10 及如下
0.7
154
2.0
20~35
L 0
220
3.0
60~110
1.5
330
4.0
停电作业线路与另一带电线路相接近或交叉,工作时也许与带电
线路带电体接触或接近至表 安全距离以内,则此带电线路亦 应停电并予接地。
接近或交叉其她电力线工作安全距离
电压级别(w)
安全距离(m)
电压级别(kV)
安全距离(m)
10 及如下
1.0
154~220
4.0
20~35
2.5
330
5.0
60~110
3.0
在交叉档内架设到县、接地线,施工线路应在带电线路下面,
并应符合表 2 安全距离规定,还必要采用防止导、地线产生跳动或 过牵引而减小安全距离办法。
在发电厂、变电所出入口处,或线路某一段有两条及以上线路邻 近施工时,应在施工线路各杆塔处作出标志,并设专人监护。
停电作业,施工负责人应向停、送电发电厂、变配电所提出停
电筹划申请,其内容应涉及:
需停电线路(设备)名称,停电范畴、地点(起止杆号)。
作业内容。
需停电起止日期及每天停电时间。
施工负责人姓名及联系办法。
停电作业应执行工作票制度。工作票签发人可由负责停、送电 变、配电所主管生产领导人、技术人员担任。工作票签发人不得兼 任该项工作施工负责人。
线路停电,发电厂、变配电所工作允许人(值班调度员)必要对 停电线路采用有效安全办法后方可发出允许工作命令。
允许开始工作命令,必要告知到施工负责人。双方应认真记录, 并应复诵核对无误。
禁止双方约时停、送电。
施工中如遇雷雨、大风或其她状况威胁到施工人员安全时, 施工负责人可决定暂停施工。
工作间断时,施工地点所有接地线应保存。如工班须暂时离 开施工地点,必要采用安全办法和派人看守。恢复工作前,施工负责 人应检查接地线等各项安全办法。
、工作结束后,施工负责人(涉及小组负责人)必要检查施工地段 和线路上有无遗留工具、材料等,并查明所有施工人员已由杆塔上 撤下后,方可命令拆除接地线。接地线拆除后,不得再登杆施工。