文档介绍:Chapter 3-6 - Fire Protection Standard for Correctional Institutions
(Publié aussi en français sous le titre Chapitre 3-6 - Normes sur la protection contre l'incendie pour les établissements de détention)
Table of Contents
1. General 1
2. General requirements 3
3. Construction 4
4. Occupancy hazards 6
5. Fire protection systems 7
6. Water supplies 10
7. Electrical 11
8. Emergency procedures 12
9. munication and control munication equipment room (mccp/cer) 13
Appendix A 14
Appendix B 18
Appendix C 20
1. General
Purpose
This standard prescribes fire protection requirements for correctional institutions to minimize risks to life and property and to protect and conserve the Government's financial position.
Application
This standard applies to correctional institutions under the administration of the Correctional Service of Canada.
A building or structure in an institution that is used for farming purposes and not as a residence is exempt from the requirements of this standard. (See appendix A)
Community residential facilities are exempt from the requirements of this standard. (See appendix A)
Scope
The requirements of this standard apply to all new construction, including additions and alterations.
The requirements of this standard apply to existing buildings to the extent practicable. (See appendix A)
Administration
The missioner of Canada or the authorized representative of the missioner (henceforth referred to as FC) is responsible for the administration and enforcement of this standard.
This standard is not to be interpreted as permitting practices specifically prohibited by provincial, municipal, or other federal legislation.
Where reference is made to other codes and standards, unless otherwise stipulated, the reference shall be to the latest edition including amendments to that code or standard.
Definitions
Certain terms used in this standard are defined to ensure understanding of their meaning and intent.
Contai