文档介绍:Performance Analysis of a Hybrid Asymmetric Multilevel
Inverter for High Voltage Active Power Filter Applications
Miguel López G.(1) Luis Morán T.(1) José Espinoza C.(1) Juan Dixon R.(2)
(1) Dept. of Electrical Engineering (2) Dept. of Electrical Engineering
Universidad de Concepción Universidad Católica de Chile
Casilla 160 – C Casilla 306 – Correo 2
Concepción – Chile Santiago – Chile
Phone: 56 – 41 – 203514 Phone: 56 – 2 – 686 4278
Fax: 56 – 41 – 246999 Fax: 56 – 2 – 5524054
Email: ******@ Email: ******@
Abstract – An active power filter implemented with multiples high voltage power distribution systems. A simple three-phase
single-phase full bridge voltage-source inverters connected in power distribution transformer is mended for isolation
series (known as cascaded hybrid asymmetric multilevel inverter and to be used as a link reactor.
or binary multilevel VSI) is presented and analyzed in this paper.
The proposed active power filter is aimed pensate current a b c
ponents in medium and high voltage power
distribution systems. A control scheme is developed to allow the
operation of the inverter modules at different voltages and
switching frequencies. Also, a simple method to calculate the XL XL XL
reference signal for each inverter is proposed. Simulated
waveforms for steady-state and transient o