暖通空调 HV &A C 2006 年第 36 卷第 9 期设计参考· 56 ·
某别墅地埋管地源热泵空调
系统设计与测试分析
河北工程技术高等专科学校高2 桂芝☆王桂娟
3 沧州市建筑设计研究院田继民
摘要介绍了该别墅地埋管地源热泵空调系统中地埋管换热器的计算方法。给出了一组
冬季和夏季的运行数据。数据表明,该空调系统的供热量、制冷量、性能系数等基本能达到设
计指标,冬季的换热器吸热量略小于设计值,应考虑适当的余量。
关键词地源热泵系统别墅测试分析
De si g n a n d t e st of t h e gro u n d h e a t e x c h a n g e r
gro u n d s o urc e h e a t p u m p s yst e m f or a vill a
By Gao Guizhi ★, Wang Guijuan and Tian Jimin
Abst ra ct Presents t he calculating met hod of ground heat exchanger in t he ground source heat p ump
system. Rep resents t he operating data in summer and winter of a year. As a result , t he heating capacity ,
cooling cap acity and CO P of t he system can meet t he design conditions , and t he heat charge cap acity of t he
heat exchanger is slightly smaller t han t he design condition , and an app rop riate allowance should be
considered.
Keywords ground source heat p ump system , villa , test , analysis
★ Hebei Engineering and Technical College , Cangzhou , Hebei Province , China
①
建筑位于沧州颐和庄园小区内,建筑面积为表 2 室内设计参数℃
512 m2 ,共 3 层。结构形式为砖结构,外墙为 370 夏季温度冬季温度
mm 普通砖墙贴外墙砖,外门窗选用彩板门窗,玻起居室、客厅 26 ± 2 20 ± 2
卫生间± ±
璃为中空玻璃。 28 2 22 2
1 设计参数及负荷 1. 2 冷热负荷
1. 1 设计参数通过计算,建筑物的冷热负荷结果见表 3 。
依据现行的《采暖通风与空气调节设计规范》表 3 建筑物的冷热负荷计算结果 kW
最大设计冷负荷平均冷负荷最大设计热负荷平均热负荷
( GB 50019 —2003) [1 ] ,室内外的设计参数见表 1 ,
48. 4 31. 3 37. 6 24. 6
2 。
表 1 室外设计参数