文档介绍:干式电抗器绕组直流电阻不平衡率与导线断股情况分析
[摘要]本文从电抗器的结构、绕制电抗器所用导线根数及导线截面积等因素出发,阐述了绕制电抗器所用导线根数的不同,断股后其对直流电阻不平衡率的影响也各不相同的理论,并将这一理论应用到实际工作中。同时推导出电抗器断股后其直流电阻不平衡率的上限计算公式,在实践中,这一理论得到了检验,从而提高了通过试验值来判断电抗器运行状态的准确性。
[关键词] 电抗器;导线根数;直流电阻;不平衡率;规程规定
[abstract] This article from the reactor structure,wire root number and wire section area,expounds the theories that the influence of the unbalance rate of Dc resistance is different with the difference of the number of reactor wire roots after the reactor is broken,and the theory was applied to practical the same time,a formula on the upper unbalance rate of Dc resistance after the reactor broken was practice,this theory was applying this formula,the judging accuracy on the running state of the reactor was improved.
[key words] reactor;wire root number;Dc resistance;unbalance rate;Regulations sets
1、前言
电抗器作为无功补偿的手段,在电力系统中是不可缺少的。并联电抗器是并联连接在系统上的电抗器,主要用以补偿电容电流。在超高压远距离输电系统中,通常将其安装在变压器的三次线圈上,用以补偿长距离输电线路的电容性充电电流,防止系统出现线端电压升高,降低系统操作过电压,抑制电网谐振过电压等众多功能,从而维持系统电压稳定,提高系统的传输能力和效率。
目前,随着并联电抗器的普遍应用,其存在的问题也不断暴露出来。2010年以来,在某电网公司中应用的45台35kV干式并联电抗器,共发生了4次烧损故障,这不仅暴露了该系列产品在设计、制造工艺和质量控制方面存在问题,同时也给我们提出了要确保并联电抗器安全运行必须采取新的措施和更加有效的试验判断标准。
2、干式电抗器的结构
目前广泛应用的干式电抗器,其绕组选用小截面圆导线多股平行绕制,制成多层同心式筒形线圈,每根导线表面都用多层绝缘性能良好的聚酯薄膜进行半叠绕包,所有导线引出线全部用氩弧焊焊接在机械强度高的铝质星形接线架的星形接线臂上,由于其采用并联平行绕制技术,使电抗器绕组只承受匝间电位差可在户外安全可靠运行。干式空心并联电抗器由于采用多层线圈并联,这样,其导线的并联根数少则几十、多则上百,如此可把其等效为N个不同阻