文档介绍:PRESENTATION TITLE TEXT GOES HERE AT A MAXIMUM OF FOUR LINES OF TEXT
EIAA
Annual Technical Conference
2008
Presented by Kevin Harrison
Presentation
Qualification issues.
Class B and Class A wiring.
DCL B and DCL A wiring.
Alberta Building Code 2006 fire alarm systems.
Smoke Alarms
Alberta Building Code 2006 smoke alarms
Qualification
Alberta Qualification in accordance with the Alberta Fire Code
Electrician
Before Sept 1/91
Electrician
After Sept 1/91
Alarm Technician
plete
Fire detection course
Apply to ECAA for qualification number
Basic Electricity
Basic Electronics
Technical writing
Fire Detection
Apply to AFSA for qualification number
Fire Alarm System ConductorsRule 32-100
Insulation rating of not less than 300 V
Shall be suitable for the purpose of the type listed in Table 19 and individual conductors smaller than #14 AWG installed in a raceway shall be equipment wire of the type listed in Table 11.
Fire Alarm System ConductorsRule 32-100
Conductors shall not be smaller than:
a)#16 AWG for individual conductors pulled in a raceway.
b)#19 AWG for individual conductors laid in a raceway.
c)#19 AWG cable assembly of two or more conductors.
d)#22 AWG cable assembly of four or more conductors.
Wiring Methods Rule 32-102 (bustible construction)
All conductors of a fire alarm system shall be:
a) installed in a metal raceway
b) installed in a cable having a metal armour or sheath.
c) installed in rigid non-metallic conduit, where embedded in at least 50 mm of masonry or poured concrete, or installed underground.
d) installed in electrical non-metallic tubing, where embedded in at least 50 mm of masonry or poured concrete.
Wiring Methods Rule 32-102 (combustible construction)
Conductors installed bustible construction shall be installed in accordance with Section 12
a) Non-metallic sheathed cable.
b) FAS cable; or
c) installed in a totally enclosed non- metallic raceway.
Conventional Wiring
Class B wiring incorporates end of lin