文档介绍:本科毕业设计说明书
600MW发电机组主变压器继电保护
学院:机电工程学院
专业:农业电气化及自动化
姓名:
学号:
指导教师:
职称:讲师
设计完成日期:二零一三年六月
设计概况
针对600MW发电机组主变压器继电保护可能出现的故障及不正常运行状态做了较为详细的分析就变压器高低压侧出口外各种短路进行了短路电流的计算,进而提出了一套较完整的主变压器继电保护配置方案,包括瓦斯保护、纵联差动保护、复合电压起动的过电流保护、零序保护等,并对各种保护的工作原理及整定原则做了简要的介绍最后进行的整定计算和灵敏度校验,并绘制了主变压器保护配置展开图。
【关键字】:变压器;短路计算;继电保护;整定
Design Overview
In the light of the faults of 600MW generator transformer protection may occur and not the normal operation of the state to do a more detailed analysis on the low pressure side of transformer outlet short circuit of short-circuit current calculation, and then puts forward a set of plete transformer protection configuration scheme, including gas protection, longitudinal differential protection, composite starting voltage of zero sequence current protection, protection, and working principle of various protection and its setting principle is briefly introduced in the setting calculation and sensitivity check, and the configuration of main transformer protection deployment diagram
[keyword]: Transformer; Short circuit calculation; Relay protection; Setting
目录
1. 引言 1
1
1
1
2
3
4
4
4
4
5
7
8
8
8
9
当系统以最小运行方式时 10
13
13
变压器的故障和不正常运行状态分析 13
13
15
15
瓦斯保护原理 15
纵差保护原理及整定计算 20
过负荷保护的整定计算 27
复合电压起动的过电流保护的整定计算 28
零序过电流保护的整定计算 30
结束语 32
致谢 33
参考文献 34
1. 引言
电力系统在生产过程中,有可能发生各类故障和各种不正常情况。其中故障一般可分为两类:横向不对称故障和纵向不对称故障。横向不对称故障包括两相短路、单相接地短路、两相接地短路三种,纵向对称故障包括单相断相和两相断相,又称非全相运行。电网在发生故障后会造成很严重的后果:
(1)电力系统电压大幅度下降,广大用户负荷的正常工作遭到破坏。
(2)故障处有很大的短路电流,产生的电弧会烧坏电气设备。
(3)破坏发电机的并列运行的稳定性,引起电力系统震荡甚至使整个系统失去稳定而解列瓦解。
(4)电气设备中流过强大的电流产生的发热和电动力,使设备的寿命减少,甚至遭到破坏。
不正常情况有过负荷、过电压、