IEEE Guide for Abnormal Frequency
Protection for Power Generating
Plants
IEEE Power Engineering Society
Sponsored by the
Power System mittee
EEE Standards
IEEE Standards
I
Published by
The Institute of Electrical and Electronics Engineers, Inc.
3 Park Avenue, New York, NY 10016-5997, USA
Print: SH95150
27 February 2004 PDF: SS95150
IEEE Std ™-2003
(Revision of
ANSI/IEEE -1987)
IEEE Guide for Abnormal Frequency
Protection for Power Generating
Plants
Sponsor
Power System mittee
of the
IEEE Power Engineering Society
Approved 16 June 2003
IEEE-SA Standards Board
IEEE thanks the International mission (IEC) for permission to reproduce: Figure 1
on page 44 from its International Standard IEC 60034-3 “Rotating electrical machines—Part 3: Specific
requirements for turbine-type synchronous machines,” 4th Ed. 1988-08. All such extracts are copyright of
IEC, Geneva, Switzerland. All rights reserved. Further information on the IEC is available from
. IEC has no responsibility for the placement and context in which the extracts and contents
are reproduced by the author; nor is IEC in any way responsible for the other content or accuracy therein.
Abstract: This guide has been prepared to assist the protection engineer in applying relays for the
protection of generating plant equipment from damage caused by operation at abnormal
frequencies including overexcitation.
Keywords: load shedding, overexcitation, overfrequency, underfrequency
The Institute of Electrical and Electronics Engineers, Inc.
3 Park Avenue, New York, NY 10016-5997, USA
Copyright © 2004 by the Institute of Electrical and Electronics Engineers, Inc.
All rights reserved. Published 27 February 2004. Printed in the United States of America.
Print: ISBN 0-7381-3732-4 SH95150
PDF: ISBN 0-7381-3733-2 SS95150
No part of this publication may be reproduced in any form, in an e