文档介绍:冬季供暖工况下混凝土辐射顶板传热特性
摘要:针对冬季供暖工况下混凝土辐射顶板的传热问
题,建立顶板辐射供暖的简化数学模型,利用 MATLAB软件 计算其供热量,并通过该顶板辐射供暖的热工特性实验验证
模型的合理性。研究表明:顶板温度计算值与实验结果的误
差在 %以内, 供热量计算值与实验结果的误差在 515%左
右。通过对实验和计算结果的分析发现:在定流量稳态工况
下,顶板温度随供水温度的增大呈指数性增大,随换热盘管 间距的增大而减小。
关键词:辐射供暖;传热;供热量;数学模型;实验验
证
中图分类号:
文献标志码: A 文章编号: 16744764 (2016) 02011807
Abstract : A simplified mathematical model was established to calculate the heating transfer capacity through MATLAB program. Compared with the results of thermal performance test , the mathematical model was reasonable with a maximum error less than %. According to the results of model and experiment , in the constant flow condition ,
heating capacity of the ceiling increases as the temperature increases, meanwhile heating capacity decreases as the heat exchange coil spacing increases.
Keywords : ceiling radiant heating panel ; heat transfer ;
heating capacity ; mathematic model ; experimental validation
辐射板空调系统以其节能、环保、低噪声 [1] 、房间无明
显吹风感 [2] 、热舒适性高 [3] 及节省建筑空间等优点逐渐成
为人们新的选择,与传统空调相比可节省全年能耗 30%以上
[4]。 2002 年美国能源部将其作为未来最有优势的 15项暖通
空调节能技术之一 [5]。现代空调技术起源于欧洲, 20 世纪
70 年代瑞士率先推出用于低温地板辐射采暖的交联聚乙烯
管材,大大促进了辐射采暖空调的发展 [6] , 20 世纪 80 年代
末,低温地板采暖技术已经被广泛应用于住宅以及商场、饭
店等民用及公共建筑, 20 世纪 90 年代初鲁诺 ?凯勒教授设计
的混凝土顶板辐射采暖制冷成功运行,使建筑集供冷采暖为
一体技术得以实现,减少了设备占有建筑空间和设备初投资。
目前,可采用加隔热保温层等措施来降低混凝土背面的热损
失,降低建筑结构内外温差。如果是高层建筑,对每一层的
室内来讲,相当于地面和顶面双层供暖,混凝土楼板具有较
大蓄热能力,较低的供水温度就可满足人体热舒适要求,因