文档介绍:of rural drinking water sources, protection of drinking water sources in rural areas by the end of the delimitation of tal drinking water sources, protection of drinking water sources in rural areas by the end of the delimitation of the scope of protection, complete with warning signs, isolating network protection facilities
of rural drinking water sources, protection of drinking water sources in rural areas by the end of the delimitation of the scope of protection, complete with warning signs, isolating network protection facilities
of rural drinking water sources, protection of drinking water sources in rural areas by the end of the delimitation of the scope of protection, complete with warning signs, isolating network protection facilities
2影剧院、体育馆、展览馆、礼堂、公共娱乐场所、建筑面积大于1000m2的商店〔开敞、半开敞式菜市场除外〕、建筑面积大于500m2的餐饮服务场所等人员聚集的单层、多层公共建筑或场所;
3医院、疗养院、康复中心、幼儿园、托儿所、养老院〔老年公寓〕等单层、多层医疗保健和婴幼老弱残障人员服务设施;
4候机楼、长途汽车客运站、公共交通枢纽、火车站、地铁车站等公共服务设施;
5车位不少于50辆的单建、附建汽车库;
6综合楼、写字〔办公〕楼、旅馆、图书馆、档案馆、教学楼、科研楼、学生宿舍楼等其他多层公共建筑或场所;
7地下、半地下民用建筑〔包括地下、半地下室〕及平战结合的人民防空工程。
消防安全标志设置
设置电光源型消防安全疏散标志时,应符合以下要求:
1电光源型消防安全疏散标志应采用不间断电源〔UPS〕供电、并宜采用相对集中的供电方式〔可按楼层、防火分区等划分供电区域〕,当数量较少、分置分散时可采用自带电源供电;
2对于一类高层民用建筑、候机楼、公共交通枢纽、火车站、地铁车站、大中型体育馆和商店及每层建筑面积大于3000m2的其他大型公共建筑,地下建筑、人防工程,其应急电源的连续供电时间不应小于30min;对于其他建筑,不应小于20min;
3标志外表的平均亮度宜为17~34cd/m2,但任何小区域内的亮度不应大于300cd/m2且不应小于15cd/m2,最大亮度与最小亮度之比不应小于5:1;
4设置间距不应大于20m。